25
CHAPTER 6 GENERAL FUNCTIONS
The general functions determine the operations of the AD-4401 and are all stored in the EEPROM. Each function is
sorted into the groups by capabilities and represented by prefixing a function number (F-XX) with its group name. This
chapter describes how to set the general functions and their details. For functions related to options, see the descriptive
sections for the options.
SETTING METHOD
Step 1 With the [ENTER] key pressed and held, press the [SETPOINT] key. “Fnc” is displayed to inform you that
the indicator is entering the general function mode.
• Note: When you did not want to enter the function mode, press the [ESC] key. The indicator will return to the
normal mode.
Step 2 Press the [ENTER] key. The indicator will switch to the general function mode and the cursor appears at
the letter, “c”.
Step 3 Select the target function group, using the [ ∧ ] , and [ ∨ ] keys
After selecting the function group, press the [ENTER] key. (In this example, select Basic Capabilities
Related)
The main display section displays the function number and the cursor appears in the lowest digit. The
Subdisplay section displays a set value for the function.
Group Name Symbol
Basic Capabilities Related Fnc
Weighing Sequence Related Sq
Control I/O Input Related in
Control I/O Output Related out
Standard Serial Output Related si
Parallel BCD Output Related bcd
RS I/O Related rS
Setpoint Value input Related SP
Analog Output Related An
Step 4 Using the [<], [>], [ ∧ ] , and [ ∨ ] keys, select the function number you want to set. In this example, select
FNCF-02. For your information, FNCF-02 is a capability of the [F] key.
Step 5 In this example, set the [F] key to a “print command.” Press the [ENTER] key. The Subdisplay section
starts blinking.
Step 6 Press the [ ∧ ] key. The Subdisplay section displays “1”.
Step 7 Press the [ENTER] key. The main display section starts blinking and you are returned to Step 4, selection
of the function number.
Step 8 Press the [ESC] key. The function number disappears and you are returned to Step 2.
Step 9 Press the [ESC] key again. The settings so far are saved in the EEPROM and the indicator is returned to
the normal mode.
Comentários a estes Manuais